This paper describes a ventilation control system designed using off-the-shelf components. The system has outputs for two fans, inputs for two wind meters, a power switch, a touchscreen monitor, and three warning indicators. The system measures air flow within ± 1 f/m using the WeatherFlow wind meters. The microprocessor used to control the system offers manual or automated control. The automated system maintains air flow within ± 24 f/m and can re-establish air flow within 160 seconds of partial air flow blockage